Collection ZYD-I Transformer Oil Regeneration Method
Application:
ZYD-I device is specifically developed for on website use to entirely regenerate insulating oils in energized or de-energized transformers. It not only provides typical oil purification including degassing, drying and particulate elimination but also removes acidity, sludge, other soluble oil decay products, and increases shade. For specific software, the program also can be mounted on a leak proof foundation or be installed and operated on a trailer.
Features:
one. For unique software, the procedure can be managed by P.L.C (Programmable Logic Controller) (ZYD-I-A Series).
2. Special vacuum dehydration, degassification and regeneration technique, undertake stereo-evaporation technology. Duplex 3D stereo-evaporation, eliminating the liquid water rapidly
three. British isles g technology by which the trace water that is demonstrate chain, such as dissolved h2o, can be removed effectively.
four. Superior infrared liquid-degree automated management program to attain totally automated management.
five. Can be applied for vacuum oiling and drying electricity transmission products.
six. Special additives for depolarization can get well oil shade of aged transformer oil to new.
CZPT Parameter:
Parameter | Device | ZYD-I-thirty | ZYD-I-fifty | ZYD-I-100 | ZYD-I-a hundred and fifty | ZYD-I-two hundred | ZYD-I-250 | ZYD-I-three hundred | |
Movement fee | L/h | 1800 | 3000 | 6000 | 9000 | 12000 | 15000 | 18000 | |
Working vacuum | MPa | -.08~-.099 | |||||||
Operating strain | MPa | ≤0.3 | |||||||
Temperature selection | ºC | 20 ~ 80 | |||||||
Electricity | 3 ph 380V 50Hz (Or as needed) | ||||||||
Operating sounds | dB(A) | 75 | seventy five | seventy five | 75 | eighty | eighty | 80 | |
Heating energy | kW | thirty | 30 | 45 | sixty | seventy five | 90 | one hundred twenty | |
Complete energy | kW | 35.five | 37.5 | fifty two.five | seventy one.four | 86.five | 102.five | a hundred thirty five | |
Oil Inlet/Outlet | mm | φ25 | φ32 | φ42 | φ50 | φ50 | φ60 | φ60 | |
Fat | Kg | 600 | 800 | 1050 | 1400 | 1800 | 2000 | 2200 | |
All round | Length | mm | 1050 | 1100 | 1200 | 1450 | 1600 | 1800 | 1900 |
Width | mm | 750 | 800 | 950 | 950 | 1100 | 1200 | 1200 | |
Peak | mm | 1350 | 1400 | 1500 | 1650 | 1800 | 1900 | 1900 |
Product | Device | Right after treatment method |
Breakdown Voltage | kV | ≥75 |
Moisture articles | PPM | ≤3 |
Gas material | % | ≤0.1 |
Impurity dimensions | micron | ≤1 (no free carbon) |
IFT | dynes/cm | ≥40 |
Acid price | mg KOH/g | ≤ .03 |
Dielectric decline variables | tgδ(90ºC) | ≤0.001 |